Chart #1
Steam Line Material
INSTALLATION
RECEIVING & UNPACKING EQUIPMENT
Steam
Hose
Copper Tube Stainless
Steel Tube
1.
2.
Check packing slip to ensure ALL material
has been delivered.
Short run
< 10 feet
(3 m)
ü
ü
ü
ü
ü
ü
All material shortages are to be reported to
Walter Meier (NORTEC) within 48 hours
from receipt of goods. Walter Meier
(NORTEC) assumes no responsibility for
any material shortages beyond this period.
Long run
> 10 feet
(3m)
DI / RO
water
3.
4.
Inspect shipping boxes for damage and
note on shipping waybill accordingly.
After unpacking, inspect equipment for
damage and if damage is found, notify the
shipper promptly.
4.
5.
Consult the following pages for step by step
distributor installation starting with Figure
#1.
5.
6.
All NORTEC products are shipped on an
F.O.B. factory basis. Any and all damage,
breakage or loss claims are to be made
directly to the shipping company.
Consult the charts below for steam and
condensate sizing guidelines when using
steam distributors.
Chart #2
Recommended material and size for steam run
Each distributor is provided with: installation
manual, one hose cuff, and two hose
clamps.
Load
Steam Run
Steam
Line
Steam Line
Description
PRE-INSTALLATION CHECK
Material
lb/hr kg/hr
ft
m
1.
Ensure the total capacity of the humidifier is
not higher than the allowable maximum
steam capacity of the distributors used.
ASD 10: 22 lbs/hr (8 kg/hr)
Copper 3/4" MED-L Tubing
tube (7/8" O.D.)
Copper 1” MED-L Tubing
0-30
0-30
0-30
0-30
0-13 0-10 0-3
0-13 10 + 3 +
0-13 0-10 0-3
0-13 10 + 3 +
ASD: 25 lbs/hr (9 kg/hr)
BSD: 35 lbs/hr (13 kg/hr)
CSD: 115 lbs/hr (45 kg/hr)
tube
(1 1/8" O.D.)
7/8” tube x
Stainless
Steel tube
0.049” thick.
Stainless 1 1/8” tube x 0.049”
Steel tube thick.
STEAM LINE INSTALLATION
Copper 1 ½” MED-L Tubing
tube (1 5/8" O.D.)
30-100 13-45 0-20 0-6
GUIDELINES
Copper 2” MED-L Tubing
1.
2.
Nortec steam hose should only be used on
short steam runs below 10 feet.
30-100 13-45 20 + 6 +
30-100 13-45 0-20 0-6
30-100 13-45 20 + 6 +
tube
(2 1/8" O.D.)
1 ¾” tube x
0.065” thick.
2” tube x
Stainless
Steel tube
Stainless
Steel tube
Ensure that no condensate produced in the
steam line will remain trapped. Steam
naturally flows upward and condensate
naturally flows downward.
0.065” thick.
Please note that options shown in a bold-italic font requires
that reducers be used at both ends. These extra large sizes are to
allow for better condensation removal in long steam runs. These
sizes will not permit you to use hose coupling to connect your
self to either humidifier or distributors.
3.
See material recommended for use in the
chart below. To eliminate the metal
corrosion, Nortec does not recommend the
use of steel piping.
- 1 -